CIRCUIT INPUT (Motor Loads)

Enter the breaker size, circuit description, and a M to identify this load as a motor load. 

  

Math Example (1-Phase)

If the load is 12 amps at 208 volts

( 12A x 208V ) = 2,496 VA

( 2,496 VA ÷ 2 ) = 1,248 VA (on each leg)

 

  

Math Example (3-Phase)

If the load is 18 amps at 208 volts

 ( 18A x 208V x 1.732 ) = 6,480 VA

( 6,480 VA ÷ 3 ) = 2,160 VA (on each leg)

 