ENTERING LOADS

 
 -  Receptacle Loads

Enter the breaker size, circuit description, and a D to identify this load as receptacle diversity load.

  
Math Example (1-Phase)
 A circuit has 8 receptacles at 180VA each.
 If the load is 12 amps at 208 volts
 ( 180VA x 8 ) = 1,440 VA
 
The program calculates the first 10,000 VA of receptacle load at 100% and the remainder at 50%. 
 